Astroflame Passive Fire Protection Products

Trade Name: ASTRO X-SERIES PILLOW

Fire Pillows

Fire Protection Certification Logos

Fire Pillows tested with metallic pipes, cables, cable bunches, cable trays and cable ladders.

Fire Resistance EN 1366-3 EI 120 and BS 476 - 240mins.

Fire Classification EN13501-2.

IET (IEE) 17th Edition Fire Stop Compliant
to Regulation 527.1-3 - Electrical Installations.

BS 7671-2008 Chapter 42 & 52 - Electrical Installations Fire Resistance.

Acoustic Isolation EN10140 - 46dB.

Air Permeability EN1026 - 420Pa.

Reaction Temperature 180°C.

Expansion of 200%.

X-Series Intumescent fire pillows

Description

X-Series Fire Pillows are designed to provide an effective fire barrier, on a temporary or permanent basis, for services which are CE Certification X-Pillowssubject to frequent changes or replacement. The fire pillows consist of a waterproof glass cloth bag containing organic fillers and intumescent additives.

Pillows can be added, removed or rearranged in an aperture to accomodate to the needs of the situation and have been tested with metallic pipes, cables, cable bunches, cable trays and cable ladders.

Tested in block wall, concrete and masonry walls and concrete floors up to 1m² area and suitable for indoor and outdoor locations pillows remain flexible between –20°C to +130°C.

Non-toxic, easy to install and with a 25 year lifespan.

Three sizes of X-Series fire pillow are available; please ensure that the correct pillow is installed to suit the opening size. See tables below.

CE InformationCE Marked Documents
'DoP's are Declarators of Performance
'CoC's are 'Certificates of Constancy'

DoP X Series Fire Pillows CoC X Series Fire Pillow

X Series Fire Pillow TDS

ul-eu_certification
UL Documentation

 

Properties & Specifications

Colour

Silver

Fire Resistance

EN 1366-4 EI 120, BS 476 240mins

Insulation

EN 1366-4 120mins

Classification

EN 13501-2

Acoustic Isolation

EN 10140 46dB

Air Permeability

420Pa EN 1026 - 100Pa 22.8/31.1 m3/h/m2

Pillow Dimensions & Usage Guidelines

X Fire Pillows Specification Table

To estimate the number of fire pillow required please refer to the full Installation sheet, which has tables showing quantities required for a range of fire pillow and void sizes.

Availability

Available in 3 standard sizes.

Size / Type

Dimensions

Product Code

Large

330mm x 200mm x 45mm

AFFPLX

Small

330mm x 200mm x 25mm

AFFPSX

Sausage

330mm x 50mm x 20mm

AFFPSASX

 

Packing

Large - 25 per pack
Small / Sausage - 50 per pack.

To Order & Specify

Please quote - Quantity/Trade Name / Product Ref./ Size
Typical example:-
5/ Astro Pillow / AFFPLX / Large

Fire Test and Assessment Reports.

Certifire 3rd Party Accreditation CF615.

Fire Resistance EN 1366-3 EI 120 and BS 476 - 240mins.
Fire Classification EN13501-2.

IET (IEE) 17th Edition Fire Stop Compliant to Regulation 527.1-3 - Electrical Installations.
BS 7671-2008 Chapter 42 & 52 - Electrical Installations Fire Resistance.

Acoustic Isolation EN10140 - 46dB.
Air Permeability EN1026 - 420Pa.

Health and Safety

Care should be taken to avoid puncturing the pillows as dust generated may cause irritation to skin or eyes. Wear gloves and dust mask if handling damaged pillows.

Keep out of reach of children. Normal good industrial and personal hygiene practices should be observed.

Environmental Impact

Low VOC (air quality).
No Power Tools required for installation (no energy source required).
Dust free.
Low Ozone Depletion Potential (ODP).
Low Global Warming Potential (GWP).
No water pollution.
Smoke and Air Tightness.
Noise Reduction.
Thermal Insulation.
Recycling of Packaging.
Avoidance of Air Filtration.
The life cycle of X-Series Fire Pilows is over 25 years.

Astroflame (Fire Seals) Ltd. Intumescent House