Passive fire protection products from ASTROflame
 Installation Sheet
Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below
Home Safety Data Sheets Installation Sheet Index Fire Tests Index Enquiry Form Contact Details Search Our Sites Online Orders and Quotes


CAVITY FIRE BARRIER
Trade Name: Cavity Fire Barrier on a Roll Jump to installation instructions

Introduction

The purpose of this document is to give guidance to approved contractors and suppliers who are engaged in the fire stopping of Cavities in buildings using the Astro Cavity Fire Barrier on a Roll System.

  • Passive fire protection products prevent the passage of fire, smoke and hot gases.
  • Prevent the spread of fire, smoke and hot gases through a building by containing it in the compartment of origin.
  • Maintain the integrity of escape routes from a building.
  • Reduce loss or damage to property from the effect of fire and smoke.
  • Maintain pressure differential between compartments and ventilation channels

Astro Cavity Fire Barrier

This is a high expansion intumescent strip of typical dimensions 4 mm thick x 75 mm wide and is supplied in rolls of 6.3 metres long. The strip is encased in a red pvc sleeve to provide excellent weather protection and easy identification on site.

Availability

75mm x 4mm x 6.3 Metres
Product Ref: AFCFB75

 

Installation of Cavity Fire Barrier

 

Staple to batten

If a cavity is wider than the nominal 50mm then the cavity can be reduced to 50mm or less via the use of an appropriately sized timber batten.

The Cavity Fire Barrier can then be stapled to the batten as shown on the left.


The strip should be stapled along its centre line using 14 mm long corrosion resistant staples at intervals of approximately 250mm.

Ends of the roll should be tightly butted together.



If the cavity fire barrier is cut then the pvc sleeve should be folded around the exposed end to maintain weather protection and this then stapled to the sheathing board.

 

Fitted Cavity Fire Barrier

Cavity Barrier in Situ

Expanded Cavity Fire Barrier

Cavity Barrier expanded after/during fire

 

Compliance

Astro Cavity Fire Barrier is manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000. For fire test certification contact Astroflame Fireseals technical department.

Fire Test and Assessment Reports

Fire Test and Assessment Reports
On Request

Storage and disposal

Storage and Disposal
Refer to COSHH sheet.
.

Issue 02/08

Astroflame (Fire Seals) Ltd. Intumescent House
Unit 8, The IO Centre, Stephenson Road, Segensworth
FAREHAM, ENGLAND PO15 5RU
tel 0800 023 2482
(01329 844500)
fax 0800 023 2483
(01329 844600)
intl
tel +44 1329 844500
fax +44 1329 844600

 

 

 

As part of our policy of ongoing improvements, we reserve the right to modify, alter or change product specifications without giving notice. Product illustrations are representations only. All information contained in this document is provided for guidance only, and as ASTROFLAME FIRESEALS LTD has no control over the installation methods of the products, or of the prevailing site conditions, no warranties expressed or implied are intended to be given as to the actual performance of the products mentioned or referred to, and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given of products mentioned or referred to herein.

TOP OF PAGE