INTUMESCENT Downlighter CoverNHBC and LANTAC Approval
Trade Name ASTRO DL Cover Jump to installation instructions

Introduction

The purpose of this document is to give guidance to approved contractors and
suppliers who are engaged in the fire stopping of service penetrations in fire rated
structures using the Astro DL COVER

All service holes through floors and compartment walls must be fire stopped to
prevent the passage of fire, smoke and hot gases.

  • Prevent the spread of fire, smoke and hot gases through a building by containing it in the compartment of origin.
  • Maintain the integrity of escape routes from a building.
  • Reduce loss or damage to property from the effect of fire and smoke.
  • Maintain pressure differential between compartments and ventilation channels.



THE ASTRO intumescent downlighter cover SYSTEM

Downlighers in ceilings are widely used in commercial buildings. Each ceiling is subject to fire regulations and where applicable the ceiling construction needs to be fire rated. However, once a hole has been made in the ceiling for a downlighter, the integrity of the construction and its ability to perform in a fire can be reduced significantly.

To combat this the ASTRO DL Cover has been developed to cover maximum protection for holes created by the introduction of a downlighter and to allow for maximum ease of fitting.


In a fire situation the cover expands internally to fill all the available space with a highly insulating fire resistant char. Thus, the fire is unable to penetrate the hole and the cover is able to give additional insulation protection to the ceiling void to reduce the chance of heat build up and ignition of flammable materials such as accumulated dust and insulation.

Please note: No part of the fitting should touch the inside of the downlighter cover when the cover is centrally located above the cut hole. If contact is made then a large cover is required.

Availability

SMALL 150 x 150
To suit cutout 50 —75 mm

MEDIUM 200 x 200
To suit cutout 75-100 mm

LARGE 250 x 250
To suit cutout 100-140mm

X- LARGE 300 x 170
To suit cutout 145 -270mm

XX - LARGE 350 X 230
To suit cutout 145-270 mm


Installation

To install small, medium or large cover.

Step 1

Step One:

Grasp legs firmly and roll cover into a tight cylinder. Ensure wiring loom is through slot before installation.

 Step 2

Step Two:

Keeping a tight grip on the legs, feed the cover through the cut out made for the downlighter.

 Step 3

Step Three:

Ensure cover has sprung back into its original cone shape.

(a) Grasp legs and pull down until L section clears the underside of the ceiling.

(b) Move legs out until vertical part of L section normal.is flush with the side of the cut out.

 Step 4

Step Four:

Release legs so that they grip the underside of the tile.Remove the excess of both legs. Cut at point A.Once cover is in place, downlighter can be fitted as normal.

The completed installation.

Finished installation

To install X-Large or XX-Large Cover.
Flatten the cover Step One: Flatten the cover

Fold the cover

Step Two:

Fold the cover into quarters by folding it in half once ....

Fold again ..... and then folding it in half again.
Pass the folded cover through the aperture Step Three: Pass the folded cover through the aperture.
Cables may be pushed through the vent slots in the cover. Step Four:

Then fit the downlighter cover as per the manufactures's instructions - cables may be pushed through the vent slots in the cover.

Check and ensure that there is a distance of 20mm minimum between the downlighter cover and any insulation or acoustic filling in the void.

Remote gearboxes and transformers must be situated outside of the downlighter cover.

The completed installation.

A finished cover installation

Compliance

Astroflame intumescent downlighter covers are manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000 . For fire test certification contact Astroflame Fireseals technical department.

Fire Test and Assessment Reports

BRE to BS EN 1365-2 :200
Report no. CC 203791A.

BS 476 Part 22 1987.
Report no. CHILT/A02166B

BS 476 Part 23 1987.
Report no. FEA/F00063
LANTAC Building Control Approval.
NHBC Type Approval.

Storage and disposal

Astro DL Covers should be stored indoors. No shelf life is given as this product will not deteriorate in storeage.

For additional testing, certification or technical information please contact ASTROFLAME FIRESEALS LTD.

Issue 01/03

As part of our policy of ongoing improvements, we reserve the right to modify, alter or change product specifications without giving notice. Product illustrations are representations only. All information contained in this document is provided for guidance only, and as ASTROFLAME FIRESEALS LTD has no control over the installation methods of the products, or of the prevailing site conditions, no warranties expressed or implied are intended to be given as to the actual performance of the products mentioned or referred to, and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given of products mentioned or referred to herein.

 

 

Astroflame (Fire Seals) Ltd. Intumescent House
Unit 8, The IO Centre, Stephenson Road, Segensworth
FAREHAM, ENGLAND PO15 5RU
tel 0800 023 2482
(01329 844500)
fax 0800 023 2483
(01329 844600)
intl
tel +44 1329 844500
fax +44 1329 844600