Loft Cone Vapour Seal

Trade Names:
Jump to installation instructions ASTRO LC LOFT CONE

 

Introduction

The purpose of this document is to give guidance to approved contractors and suppliers who are engaged in the vapour sealing of service penetrations in structures using the Astro LC Loft Cone

All service holes through Ceilings must be vapour sealed to prevent the passage of condensation

 

The ASTRO LC Loft Cone System


Downlighers in ceilings are widely used in commercial & residential buildings. Each hole in the ceiling is a potential leakage point for condensation and vapours.

To combat this the ASTRO LC Loft Cone has been developed to offer maximum protection for holes created by the introduction of a downlighter and to allow for maximum ease of fitting.

Suitable for downlights with cut-out
dimensions of 50 - 100mm.

 

Installation

Step 1 Step 2 Step 3

Step 1

Make a small hole or slit in the Loft Cone for the cable.

Step 2

After placing cover over downlight, pass cable through Loft.

Cover and seal up any holes or slits with silicone sealant

Step 3

If insulation level will not completely cover or bury Loft Cone, the transformer can be located on the top of the cover, securing with a nylon cable tie

 

Step 4 Step 5 Step 6

Step 4

Seal around base of Loft Cone with silicone sealant to secure in place

Step 5

If insulation will cover or bury the Loft Cone, the transformer must be mounted clear of insulation following transformer manufactuers recommendations

Step 6

NB. The Loft Cone is approved for installation in contact with combustible surfaces, eg timber.

The downlight must be min. 25mm away from joist.

Fit the downlighter cover as per the manufacture's instructions -

Remote gearboxes and transformers must be situated outside of the Loft Cone.

Please note: No part of the fitting should touch the inside of the downlighter cover when the cover is centrally located above the cut hole.

 

Compliance

Astro LC Loft Cones are manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000 . For test certification contact Astroflame Fireseals technical department.

Storage and disposal

Astro Loft Cone should be stored indoors. No shelf life is given as this product will not deteriorate in storage.

For additional testing, certification or technical information please contact ASTROFLAME FIRESEALS LTD.