FIRE RATED LUMINAIRE CANOPY
Trade Name ASTRO LUMI CANOPY Jump to installation instructions

Introduction

The purpose of this document is to give guidance to approved contractors and suppliers who are engaged in the fire stopping of fire rated structures using the Astro LUMI Canopy.

All service holes through floors,ceilings and compartment walls must be fire stopped to prevent the passage of fire, smoke and hot gases.

The key points for passive fire protection products are :-

  • Prevent the spread of fire, smoke and hot gases through a building by containing it in the compartment of origin.
  • Maintain the integrity of escape routes from a building.
  • Reduce loss or damage to property from the effect of fire and smoke.
  • Maintain pressure differential between compartments and ventilation channels.

THE ASTRO LUMI CANOPY SYSTEM

Astroflame luminaire canopies are designed to specifically stop the passage of smoke and fire through a fire rated ceiling,where recessed downlights are fitted.


Tests have shown that, without the canopy in place, fire and smoke would penetrate through the recessed light fitting in seconds spreading into the void or room above endangering both lives and property.

The Astro Lumi Canopy will provide 60 minutes protection by completely containing the fire and smoke within the cover,whilst at the same time allowing the heat from the light fitting to dissipate through the cover

Fully tested to BS Standard 476 part 20 & 23 clause 5
The Astro Lumi Canopy also meets the requirements of class 0 materials

Key points:

60 min rated
LPC accredited
Lightweight
Self supporting
Resistant to tear and abrasion
Simple to install
Can be fitted within minutes
Suitable for suspended and modular ceilings

 

Availability

ASTRO LUMI CANOPY sizes:
Square 300mm x 300mm x 150mm weight 0.7 kg
Square 600mm x 300mm x 150mm weight 0.9kg
Square 600mm x 600mm x 150mm weight 1.0 kg
Square 1200mm x 300mm x 150mm weight 1.0 kg
Square 1200mm x 600mm x 150mm weight 1.8 kg

Packing

Supplied single or boxes of 10

Installation

To install a luminaire Astro Lumi Canopy into a suspended grid system

Remove from packaging and unfold.

 

Remove from packaging and unfold.


Place over the luminaire fitting

Place over the luminaire fitting and align cable entry with cable.

Thread cable through cable access eyelet Thread cable through cable access eyelet as shown.
Secure the Lumi Canopy

Secure the Lumi Canopy to ceiling grid with self tapping screws (provided) by screwing through the canopy and into the bulb of the grid at 80mm centres

Fold corner tab


Fold corner tab tightly over grid section and secure.

 


 

Finished installation The canopy is now installed
Replace the surrounding tiles and finish installation

Replace the surrounding tiles and finish installation of luminaire as recommended by the manufacturer

 

For dual cable access remove the sealing bolt as shown All Astro Lighting Canopies have single or dual cable access, for dual cable access remove the sealing bolt as shown.

 

Compliance

Astro Lumi Canopies are manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000. For fire test certification contact Astroflame Fireseals technical department.

Fire Test and Assessment Reports

BS 476 part 20 & 23 by LPC (Loss Prevention Council)

Storage and disposal

Astro LUMI Canopies should be stored indoors. No shelf life is giving as the canopies will deteriorate in storage.


Disposal please refer to cosh sheet

For additional testing, certification or technical information please contact ASTROFLAME FIRESEALS LTD.

Issue 01/03

As part of our policy of ongoing improvements, we reserve the right to modify, alter or change product specifications without giving notice. Product illustrations are representations only. All information contained in this document is provided for guidance only, and as ASTROFLAME FIRESEALS LTD has no control over the installation methods of the products, or of the prevailing site conditions, no warranties expressed or implied are intended to be given as to the actual performance of the products mentioned or referred to, and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given of products mentioned or referred to herein.

 

Astroflame (Fire Seals) Ltd. Intumescent House
Unit 8, The IO Centre, Stephenson Road, Segensworth
FAREHAM, ENGLAND PO15 5RU
tel 0800 023 2482
(01329 844500)
fax 0800 023 2483
(01329 844600)
intl
tel +44 1329 844500
fax +44 1329 844600

 

TOP OF PAGE