Passive fire protection products from ASTROflame
 Installation Sheet
Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below
Home Safety Data Sheets Installation Sheet Index Fire Tests Index Enquiry Form Contact Details Search Our Sites Online Orders and Quotes

 

Jump to installation instructionsPutty Pad alternative -
Intumescent Fire Rated & Acoustic Socket Box Insert

Trade Names: ASTRO FRA Socket Box Insert

 

Introduction

The purpose of this document is to give guidance to approved contractors and suppliers who are engaged in the fire stopping of service penetrations in fire rated structures using the Astro FRA Socket Box Insert

All service holes through ceilings must be fire stopped to prevent the passage of fire, smoke and hot gases.

Prevent the spread of fire, smoke and hot gases through a building by containing it in the compartment of origin.

Maintain the integrity of escape routes from a building.

Reduce loss or damage to property from the effect of fire and smoke.

Maintain pressure differential between compartments and ventilation channels.

 

The Astro FRA Socket Box Insert

The Socket Box Covers have been developed to provide maximum protection for penetrations created by the introduction of both single and double recessed switch / socket boxes and to allow ease of fitting. In a fire situation, the cover expands internally to fill all of the available space with a fire resistant highly insulating char.

The fire is unable to penetrate the hole and the cover is able to give additional insulation protection to the wall void by reducing the chance of heat build up and the ignition of flammable structural members. The penetration in the wall also provides a path for air, thus creating heat loss and drafts, the fitting of a Astro FRA Socket Box Insert reduces this problem.

 

Installation

1. Pull through cable and make a small hole through insert.


2. Pass cable through insert and fit insert into socket box.

 

3. Fit socket cover as normal, screws can pass though the insert material

.

 

4. The flange of the insert should be hidden by the socket cover - any rough edges can be trimmed.

Note: The Socket Insert must be installed so that the flange sits proud of the plasterboard.

Sizes

To suit Single or Double socket boxes


Compliance

Astro FRA Socket Box Inserts are manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000 .

Fire & certification Tests

Astro FRA Socket Box Inserts have been tested to BS476 part 20 in an un-insulated plasterboard wall construction for 120 minutes without failure in either insulation or integrity.

For fire test certification contact Astroflame Fireseals technical department.

Acoustically tested by Sound Research Laboratories to both BS EN150 140-3: 1995 & BS 2750 Part 3 1995.

Availability

Available in singles or boxes of 10

Storage and disposal

For long term storage and ease of installation, it is recommended that the product should be stored indoors. No shelf life is given as this product will not deteriorate in storage.

For additional testing, certification or technical information please contact ASTROFLAME FIRESEALS LTD.

For additional information please contact Astroflame Fireseals Ltd.


Issue 06/08


Astroflame (Fire Seals) Ltd. Intumescent House
Unit 8, The IO Centre, Stephenson Road, Segensworth
FAREHAM, ENGLAND PO15 5RU
tel 0800 023 2482
(01329 844500)
fax 0800 023 2483
(01329 844600)
intl
tel +44 1329 844500