Passive fire protection products from ASTROflame
 Installation Sheet
Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below Click icon below
Home Safety Data Sheets Installation Sheet Index Fire Tests Index Enquiry Form Contact Details Search Our Sites Online Orders and Quotes

NHBC and LANTAC ApprovalASTROFLAME THERMAL FIRE PIPE SLEEVE
Trade Name ASTRO THERMAL FIRE PS Jump to installation instructions

Introduction

The purpose of this document is to give guidance to approved contractors and suppliers who are engaged in the fire stopping of service penetrations in fire rated structures using the Astro Wrap

All service holes through floors and compartment walls must be fire stopped to prevent the passage of fire, smoke and hot gases.

  • Prevent the spread of fire, smoke and hot gases through a building by containing it in the compartment of origin.
  • Maintain the integrity of escape routes from a building.
  • Reduce loss or damage to property from the effect of fire and smoke.
  • Maintain pressure differential between compartments and ventilation channels.

THE ASTRO THERMAL FIRE PS SYSTEM

The sleeve is a cost effective product for the fire stopping of pipe penetrations e.g. plumbing pipe and metallic pipes whilst maintaining similar thermal and acoustic properties as standard mineral fibre insulation.these properties ensure compliance to water bye laws and building regulations for cold and hot water pipes and heating systems

In a fire situation the sleeve expands to fill the available space between the pipe and the penetration.

In the case of plastic pipes the sleeve will crush and close off the pipe forming a solid char and preventing the passage of fire and smoke to the adajcent compartment.

Tested on the following pipe sizes to bs 476 part 20 for 2 hours. LANTAC Building Control Approval.
NHBC Type Approval.

Copper 12mm- 160mm

Mild steel 22mm - 160mm

Polybutylene 12mm - 28mm

PVC 55mm - 160mm

Test Matrix

PIPE
BLOCKWORK WALL
SOLID FLOOR
MINERAL BATT
PLASTERBOARD WALL
12MM COPPER  
160MM COPPER  
22MM MILD STEEL  
160MM MILD STEEL  
12MM POLYBUTYLENE
28MM POLYBUTYLENE
55MM PVC      
82MM PVC  
110MM PVC  
160MM PVC      

 

Availability

SIZE
CODE 2 Hour
SIZE
CODE 2 Hour
17mm
IPS17/2E
67mm
IPS67/2E
21mm
IPS21/2E
76mm
IPS76/2E
27mm
IPS27/2E
80mm
IPS80/2E
34mm
IPS34/2E
89mm
IPS89/2E
42mm
IPS42/2E
108mm
IPS108/2E
48mm
IPS48/2E
114mm
IPS114/2E
54mm
IPS54/2E
140mm
IPS140/2E
60mm
IPS60/2E
169mm
IPS169 /2E
Length 300mm. Wall thickness 27mm.


Please quote - Quantity/Product Ref./Colour/Length etc., eg:-

100no / ASTROFLAME THERMAL FIRE PS / 54MM

Packing

Packed as singles or in boxes of 12.

Installation

.

1

CAREFULLY CUT THERMAL FIRE PS TO REQUIRED LENGTH

CAREFULLY CUT THERMAL FIRE PS TO REQUIRED LENGTH

2

IF NECESSARY MAKE SINGLE SLIT ALONG SLEEVE LENGTH TO ALLOW FITTING AROUND INSTALLED

IF NECESSARY MAKE SINGLE SLIT ALONG SLEEVE LENGTH TO ALLOW FITTING AROUND INSTALLED

3

FIT SLEEVE AROUND PIPE AND RESEAL THE CUT WITH REPAIR TAPE

FIT SLEEVE AROUND PIPE AND RESEAL THE CUT WITH REPAIR TAPE

4

SLIDE SLEEVE ALONG PIPE AND INTO CAVITY AND TAPE SLEEVE TO EXISTING INSULATION IF REQUIRED

SLIDE SLEEVE ALONG PIPE AND INTO CAVITY AND TAPE SLEEVE TO EXISTING INSULATION IF REQUIRED

Please note : for irregular holes or gaps of greater than 15mm around the pipe sleeve fill with mortar,mastic or similar.smaller gaps can be filled with Astro Intu Mastic if required

 

Compliance

Astro Wrap are manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001:2000 . For fire test certification contact Astroflame Fireseals technical department.

Fire Test and Assessment Reports

BS Standard 476 part 20/22 2 Hour rated at Chilterm International Fire. 132 minutes integrity and insulation.

Storage and disposal

For long term storage and ease of installation, it is recommended that the product should be stored indoors. No shelf life is given as this product will not deteriorate in storage.

For additional testing, certification or technical information please contact ASTROFLAME FIRESEALS LTD.

Issue 08/03

As part of our policy of ongoing improvements, we reserve the right to modify, alter or change product specifications without giving notice. Product illustrations are representations only. All information contained in this document is provided for guidance only, and as ASTROFLAME FIRESEALS LTD has no control over the installation methods of the products, or of the prevailing site conditions, no warranties expressed or implied are intended to be given as to the actual performance of the products mentioned or referred to, and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given of products mentioned or referred to herein.

 

 

Astroflame (Fire Seals) Ltd. Intumescent House
Unit 8, The IO Centre, Stephenson Road, Segensworth
FAREHAM, ENGLAND PO15 5RU
tel 0800 023 2482
(01329 844500)
fax 0800 023 2483
(01329 844600)
intl
tel +44 1329 844500
fax +44 1329 844600

 

TOP OF PAGE