Astroflame Passive Fire Protection Products

Trade Name: Astro Clad Ventilated Fire Barrier

Ventilated Fire Barriers

Additional images for this product Installation Video

Creates a ventilated fire barrier within rainscreen cladding.

Tested on Timber and Masony wall cladding.

Suitable for ventilated cavities from 15mm.

Tested to BS 476Part 20 : BS EN 1363-1
to the principles of EOTA TR31.

Improves cladding performance.

30-120 minutes rating (dependent on substrate).

For either horizontal or vertical application.

 

 

Tenmat Ventilated Fire Barrier.

Description

Many rainscreen and cladding systems are designed with an open cavity to provide back ventilation. The cavity acts like an open chimney to allow for moisture dissipation and to create a back pressure to repel rain ingress.


However in a fire situation this chimney effect creates an open path for the hidden spread of fire both vertically and horizontally behind the cladding system.


The Astroflame range of fire rated cladding seals will maintain the ventilated cavity in normal conditions, leaving a continuous free air space, but in the event of a fire, the intumescent ventilated fire barrier will quickly expand to seal off the cavity to prevent the spread of fire.


Ventilated Fire Barriers for Cavities 15mm - 50mm Ventilated cladding  fire seal (Silver)

Many timber framed structures require a continuous ventilated to be maintained to dissipate moisture and prevent damp problems.

The Astroflame ventilated fire barriers have been tested in combustible timber constructions and can maintain the minimum 30 minute rating whilst allowing continuous ventilation in normal conditions.


 

 

 

 

Astro Clad – AFFRCLAD35 25mm Cavity Ventilated fire barrier. Tenmat diagram'

Astro Clad – AFFRCLAD35 was designed to meet the NHBC requirements to maintain a minimum 15mm ventilation gap in timber frame constructions.

The product has been successfully fire tested in maximum size cavities of 25mm fitted directly onto combustible breather membrane and fixed into the timber structure to provide at least 30 minutes fire rating.

Assessed Construction Type

Fire Rating

 

Horizontal

Vertical

Timber Frame

30

60

Masonry, Concrete

120

120

It can additionally achieve greater fire ratings in non-combustible structures

Size:
35mm x 4mm x1000mm encased in foil Maximum cavity size; 25mm
Maximum free area; 83%

Fire ratings:
Minimum 30 minutes in Timber Structures
120 minutes in Non-Combustible Structures


To Order
Astro Clad Silver 35mm x 4mm x 1000mm AFFRCLAD35

 

 

Astro Clad – AFFRCLAD75

50mm Cavity Ventilated Fire Barrier.Astro Clad- AFFRCLAD75 was developed following an increasing demand for a suitable product to close off larger cavities up to 50mm in timber frame constructions.

The product has been successfully fire tested in cavities up to a maximum of 50mm within both combustible timber structures and non-combustible structures to provide up to 120 minutes fire rating.

Assessed Construction Type

Fire Rating

 

Horizontal

Vertical

Brick, Block, Masonry

120

120

Aerated Concrete Block

120

120

Kingspan Kit on Concrete

120

120

Kingspan Kit on Timber

30

60

Mineral Fibre on Concrete

90

90

Mineral Fibre on Timber Frame

30

60

Timber Frame

30

60


Size:
75mm x 6mm x1000mm encased in foil
Maximum cavity size; 50mm
Maximum free area; 87%


Fire ratings:

Minimum 30 minutes in Timber Structures,
90 minutes on mineral wool over cement board
120 minutes in Non-Combustible Structures


To order:
Astro Clad Silver 75mm x 6mm x 1000mm AFFRCLAD75

Ventilated Fire Barriers for Cavities up to & over 125mm

Astro Clad – AFFRCLAD5050

Astro Clad – AFFRCLAD5050 was designed to provide a large continuous open air space for cavities up to 125mm.

Installed Rainscreen Cladding Fire Barrier.

Assessed Construction Type

Fire Rating

 

Horizontal

Vertical

Timber Frame

30

30

Masonry, Concrete

30

30

The product has been successfully fire tested to a maximum cavity size of 125mm fitted directly onto combustible breather membrane and fixed into the timber structure to provide at least 30 minutes fire rating.

 

 

125mm  Cavity Ventilated Fire Barrier.125mm cavity with phenolic insulation and 30 min. rated Ventilated Fire Barrier.

In addition the ventilated fire barrier can be fitted in between phenolic insulation to provide an effective fire barrier.


Size:
50mm x 50m x1000mm encapsulated in red polythene

Maximum cavity size:
125mm

Maximum free area:
60%

Fire ratings:
Minimum 30 minutes in Timber Structures
Minimum 30 minutes fitted between Phenolic Insulation

To order:
Astro Clad Red 50mm x 50mm x 1000mm AFFRCLAD5050

 

Astro Clad – AFFRCLADPLUS+

Astro Clad-AFFRCLADPLUS+ offers an effective fire barrier for cavities over 125mm. The product has been successfully fire tested for up to 90 minutes fitted directly onto cement board.

90 minuted rated ventilated fire barrier.

90 minute rated ventilated fire barrier used with insulated cladding.

The product not only offers a superior fire rating but also allows a continuous ventilation space of up to 44mm. This provides excellent ventilation behind the cladding whilst leaving enough free space for the installer to easily install the cladding panels after the ventilated fire barrier seal.

Assessed Construction Type

Fire Rating *

 

Horizontal

Vertical

Brick, Block, Masonry

30.60.90

30.60.90

Aerated Concrete Block

30.60.90

30.60.90

Fitted with Kingspan Kits

30.60.90.120

30.60.90.120

Mineral Fibre on Concrete

90

90

Mineral Fibre on Timber Frame

30

30

Timber Frame

30

30

* Fire rating will vary depending on cavity size.

Finish:Custom sized ventilated cavity fire barrier.
Encapsulated in red polythene

Size:
Customer specifies the required depth based on formula below
75mm x 1000mm x Total Cavity Width minus 44mm (Custom Depth)

Maximum Air Gap:
44mm

Fire ratings:
90 minutes fixed to cement board

To order:

Astro Clad Red 75mm x 1000mm x Your Custom Depth mm AFFRCLADPLUS+

 

To order & specify

Quote: Quantity /Trade name/Product ref

Typical wording: 10/ASTRO CLAD / AFFRCLAD35

Health and Safety

See COSHH Sheet.

Installation